Operating Instructions Safety Switch CES-AP-C.2-CH
13
Connection
Connect the device as shown in Figure 3. The OUT output can be connected to a 
control system as a monitoring output.
Important:
The subsystem CES-AP complies with PL e in accordance with EN 13849-1. To 
integratethe subsystemin a category 3 or 4 structure, it is necessaryto monitor 
the downstream load (the feedback loop must be monitored).
These examples show only an excerpt that is relevant for connection of the CES 
system. The example illustrated here does not show complete system planning. 
The user is responsible for safe integration in the overall system.
GND
DC 24 V
-F1
CES-AP-C.2-...
UB1
OA2
OB4
NC6
M8 plug-connector
(6-pin)
OUT5
0V3
-V1
-K1
-V2
-K2
L1
M
3
~
-M1
L2 L3
Fig. 3: Connection example CES-AP-CR2-CH/CES-AP-CL2-CH